SYMPTOM |
PROBABLE CAUSE |
RECOMMENDED
ACTION |
|
|
|
A. 3-25 Ton - Unit will not operate in the
TEST MODE - no fan, cool or heat. |
1.
No power to the unit. |
1. Check
line voltage to the unit. |
2.
No power to the UCP. |
2. Check for
24 VAC from bottom of F1 fuse to system. |
3.
UCP fuse (F1) is defective. |
3. Check for
24 VAC from top of F1 fuse to system ground. If 24 VAC is
not present, fuse is bad. |
|
|
|
B. Goes into TEST MODE runs for 15-40
seconds, then stops: |
1.
Unit has entered AFF mode |
1. See
Section 23.7 & 23.8. Check IDM, belt. (Nothing
runs) |
2.
A TCI is installed and its High-Temp input is open w/DIP sw.
#1 ON. |
2. Close
input or turn switch to OFF if not used. (Nothing
runs) |
3.
Heat pump only - fan runs 15 sec & stops |
3. Polarized
plugs not configured correctly - see Section 35.5. (Nothing
runs) |
4.
Goes into TEST MODE (UCPs LED blinks) but still will not
run. |
4. Each
output - cool 1 & 2, heat - is locked out. Troubleshoot
each circuit individually. (Only fan runs) |
|
|
|
C. 27.5 - 50 Ton - Unit will not operate in
the TEST MODE No fan, cool or heat |
1.
See test 1-3 in "A" above |
1. See
above |
2.
Auto Stop input is open |
2. Close
Auto Stop input; after 5 seconds system will
run |
|
|
|
D. Goes into TEST MODE, runs for 40 seconds,
then stops. |
1.
FFS failed to close after 40 seconds. |
1. See
Section 23.7, 23.8. Check belt, IDM |
2.
A TCI is installed and its High Temp input is open w/DIP
sw.#1 ON. |
2. Close
input or turn switch to OFF if not used. For additional
troubleshooting information on V3 see IOM. |
|
|
|
E. Unit will not heat or cool but the fan
switch operates. |
1.
ZSM is defective. |
1. Refer to
Zone Sensor Module troubleshooting, Sections 26 &
27. |
2.
Problem in ZSM wiring. |
2. Verify wiring connections between LTB and
ZSM. |
|
|
|
F. Unit heats and cools but will not control
to setpoint |
1.
ZSM is defective. |
1. Refer to
Zone Sensor Module Troubleshooting, Sections 26 &
27. |
2.
Unit is over/undersized. |
2. Look at
Section 40 for more information. |
3.
ZSM location poor. |
3. Look at
Section 40.1 for more information. |
|
|
|
G. CPR1 will not operate, ODM runs |
1.
Compressor failure. |
1. Test compressor - replace if
necessary. |
2.
CC1 contator or wiring failure |
2. Check
wires, terminals and CC1. Replace if necessary. |
|
|
|
H. CPR1 operates, ODM1 will not
operate |
1.
ODM has failed. |
1. Check wires, terminals and CC1. Repair / replace
if necessary. |
2.
ODM capacitor(s) has failed |
2. Repair
connection / replace as needed. |
|
|
|
I. CPR1 & ODM1 operates, but ODM2 will
not |
1.
OAS is out of range. |
1. Test
Outdoor Air Sensor - see Section 28.5. |
2.
ODM / capacitor has failed |
2. Repair / replace as needed. |
|
|
|
J. CPR1 and ODM1 will not operate even in the
TEST MODE, but fans run OK. |
1.
CC1 Circuit open. |
1. Check
wiring, terminals and applicable controls (CCB1, HPC1, &
WTL1) see Section 53 "Snubber Circuits". |
2.
LPC1 circuit open. |
2. Verify 24
VAC input at J2-2 - voltage should always be
present. |
3.
UCP is defective |
3. Cycle power off, then on, & try TEST MODE
again. If compressor runs, it was in a Cool Fail mode. See
Section 23.3. If compressor still will not run UCP must be
replaced. |
|
|
|
K. ODM 3 and/or 4 will not cycle. |
1.
OAS |
1. Perform
OAS Resistance/Temperature check. Replace if
necessary. |
2.
ODM3 and/or 4 capacitor has failed. |
2. Check ODM
capacitor, replace if necessary. |
3.
Wiring, terminal, or CC2 contactor failure. |
3. Check
wires, terminals, and CC2. Repair or replace if
necessary. |
4.
ODM3 and/or 4 has failed. |
4. Check
ODM, replace if necessary. |
5.
UCP is defective. |
5. Replace
UCP module |
6.
ODF2 has failed. |
6. Check for proper voltage and contact closure. ODF2
relay has a 24 VDC holding coil. If voltage is present,
replace relay. |
|
|
|
L. CPR2 and 3 (if applicable) will not
operate. |
1.
No power to CC2 and/or 3 coil. Cool Failure
Possible. |
1. Check
wiring, terminals and applicable controls (CCB2, CCB3, HPC2,
LPC2, WTL2, WTL3 |
2.
CC2 and/or 3 coil defective. Cool Failure
Indicated |
2. Verify
integrity of CC2 and/or 3 coil windings. If open or shorted
replace CC2 and/or CC3. |
3.
CC2 and/or 3 contacts defective. |
3. If 24 VAC
is present at CC2 and/or 3 coil, replace relay. |
4.
UCP is defective. |
4. 24 VAC is
not present at CC2 and/or 3 coil. Reset the Cool Failure by
cycling the service disconnect. Place the unit into Cool
Stage 2 Mode, step 4 for constant Volume or step 6 for
variable air volume, to ensure CPR2 and 3 Compressor
operation. Check input devices in #1 & #2 above, if no
controls have opened, and CC2 and/or 3 will not close,
replace UCP. |
|
|
|
M. Indoor motor (IDM) will not
operate |
1.
IDM has failed. |
1. Check
IDM, replace if necessary. |
2.
Wiring, terminal, or contactor failure. |
2. Check
wiring, terminals and F contactor. Repair or replace
terminals, or fan contactor F. |
3.
ZSM is defective. |
3. Place
unit in test mode. If the fan operates in the test mode,
test ZSM using the appropriate test. |
4.
UCP is defective. |
4. Check the
UCP fan output. Locate P2 connector, which is connected to
J2 on the UCP. Find wire 64A (Black) and measure voltage to
ground. If 24 VAC is not present on a call for fan, replace
the UCP. |
5.
Supply Fan Proving (SFP) switch has opened |
5. Check SFP
and belts, repair or replace if necessary. |
|
|
|
N. No Heat (YC’s CFM will not run, IP warms
up, GV is energized. |
1.
CFM has failed. |
1. Check
CFM, replace if necessary. |
2.
CFM capacitor has failed. |
2.
Disconnect BROWN wires from capacitor, test, and replace if
necessary |
3.
Wiring, or terminal failure. |
3. Check
wiring, and terminals. Repair, or replace if
necessary. |
4.
Heat relay H |
4. Check for
line voltage between terminals 1 & 3 on heat relay. If
voltage is present, contacts are open. Check for 24 VAC at H
coil, replace H if 24 VAC is present. |
5.
TNS2 and/or 3 has failed. (460/575 V units only) |
5. Check for
230 VAC at TNS2 and/or 3 secondary, between Y1 and Y2. If
230 VAC is not present, replace TNS2 and/or 3. |
|
|
|
O. No Heat (YC's only) CFM runs, GV
energizes, IP does not warm up. |
1.
TNS2 and/or 3 has failed. |
1. Check for
115 VAC at TNS2 and/or 3 secondary, between X1 and X2. If
115 VAC is not present, replace TNS2 and/or 3. |
2.
Wiring or terminal failure. |
2. Check
wiring, and terminals. Repair, or replace if
necessary. |
3.
IGN has failed. |
3. Verify
presence of 115 VAC at IGN L1 and L2. Check for 115 VAC
between terminals PPM4-1 and PPM4-2, and PPM5-1 and PPM5-2
(if applicable) in the gas section. If 115 VAC is present
for IP warmup, IGN is OK. If 115 VAC is not present, replace
IGN. |
4.
IP has failed. |
4. With 115
VAC applied to IP, warm up should take place. Cold
resistance of IP should be a minimum of 50 Ohms. Nominal
current should be 2.5 to 3.0 Amps. |
|
|
|
P. No Heat (YC’s only) GV does not energize,
CFM runs, IP warms up |
1.
Wiring or terminal failure. |
1. Verify
presence of 24 VAC between IGN PWR terminal to ground, if
not present, check wiring and terminals. Repair or replace
if necessary. |
2.
IGN has failed |
2. Verify
presence of 24 VAC between IGN VALVE terminal to ground, if
not present replace IGN. |
3.
GV has failed. |
3. Measure
voltage between TH and TR on the gas valve (GV). If 24 VAC
is present and the GV will not open, replace the
GV. |
|
|
|
Q. Low Heat Capacity, Intermittant Heat.
(YC's only) CFM runs in LO or HI speed only, or may not
operate at all in one speed or the other. |
1.
CFM has failed. |
1. Check
CFM, test LO and HI speed windings. |
2.
UCP is defective. |
2. Check UCP
K5 relay. Check for K5 coil voltage at solder joints CR16
above K5 on the UCP. Nominal voltage at the coil is 28 VDC.
If 28 VDC is present, COM. & N.O. contacts should be
closed, energizing DFM HI speed windings. If 28 VDC is not
present, LO speed should be energized through K5 COM. &
N.C. contacts. If voltage contradicts operation, UCP has
failed |
|
|
|
R.
No Heat (YC’s only) "Fan" selection switch on the ZSM is in
the "AUTO" position and the fan runs continuously. |
1.
TCO2 has opened. Heat Failure Indicated |
1. System
Status Failure Diagnostic Place the unit in the Heating Test
Mode, steps 6 & 7 for constant volume or step 8 & 9
for variable air volume and check the complete heating
system for failure. Make necessary reapairs or adjustments
to the unit. |
|
|
|
S. No Heat (TEs only) Electric heat will not
operate. |
1.
Heater contactor(s) have failed. |
1. Check for
24 VAC at AH, BH,CH, and DH contactor coils. If 24 VAC is
present on a call for heat, and the contacts do not close,
the contactor has failed. |
2.
Heater element temperature limit(s) is open. |
2. Check
line voltage between the element temperature limit terminals
located in heat section. If line voltage is present, the
limit is open. Repair heating unit, or replace limit(s) as
needed. |
3.
Wiring or terminal failure. |
3. Check for
wiring, or terminal failure in control and power circuit.
Repair or replace if necessary. |
4.
Heater Element(s) has failed. |
4. Check
element and circuit integrity. Repair or replace as
necessary. Replace open elements. |
5.
UCP is defective. |
5. Check UCP
heat outputs. "First stage", locate P1 connector, connected
to J1 on the UCP. Locate wire 65E at terminal P1-22, measure
between 65E and ground. If 24 VAC is present, repeat #3
above. If 24 VAC is not present, the UCP has failed. "Second
stage", Check UCP K5 relay. Measure from the common terminal
on the relay to ground, 24 VAC should be present, if not
repeat #3 above. If present, measure from the N.O. terminal
on the relay to ground. If 24 VAC is not present, the UCP
has failed. |
|
|
|
T. Evaporator coil freezes up during low
ambient operation. |
1.
System low on refrigerant charge. |
1. Leak
check, repair, evacuate, and recharge system as
necessary. |
2.
System low on air flow. |
2. Check
return air for obstruction or dirty filters. Check fan
wheels, motors, and belts. |
3.
Outdoor Air Sensor (OAS) has failed. |
3. Check OAS
at connector P1 by disconnecting P1 from J1 on the UCP.
Check resistance between P1-15 and P1-16, refer to the
Resistance versus Temperature chart. Replace sensor if
necessary. |
4.
FrostatTM has Failed |
4. Check
Frostat
Switch |